Using Intelligent Output Terminals

Oper

ations

and Monitor

ing

4–44

Analog Input Disconnect Detect

This feature is useful when the inverter receives a speed reference from an external
device. Upon input signal loss at either the [O] or [OI] terminal, the inverter normally
just decelerates the motor to a stop. However, the inverter can use the intelligent output
terminal [Dc] to signal other machinery that a signal loss has occurred.

Voltage signal loss at [O] terminal - Parameter B082 is the Start Frequency Adjust-
ment. It sets the beginning (minimum) output frequency when the speed reference
source is greater than zero. If the analog input at terminal [O] is less than the Start
Frequency, the inverter turns ON the [Dc] output to indicate a signal loss condition.

Current signal loss at [OI] terminal - The [OI] terminal accepts a 4mA to 20mA
signal, with 4mA representing the beginning of the input range. If the input current falls
below 4mA, the inverter applies a threshold to detect signal loss.

Note that a signal loss is not an inverter trip event. When the analog input value is again
above the B082 value, the [Dc] output turns OFF. There is no error condition to clear.

Option

Code

Terminal

Symbol

Function Name

Output

State

Description

06

Dc

Analog Input
Disconnect Detect

ON

when the [O] input value < B082 Start
Frequency Adjustment (signal loss detected), or
when the [OI input current is less than 4mA

OFF

when no signal loss is detected

Valid for outputs:

11, 12, AL0 – AL2

Required settings:

A001=01, B082

Notes:

The [Dc] output can indicate an analog signal
disconnect when the inverter is in Stop Mode, as
well as Run Mode.

The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.

RY

+

12 11

L

H O OI

FM CM2

Example (requires output configuration—
see page

3–46

):

Inverter output
terminal circuit

Dc

Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages

4–35

and

3–46

):

AL0

AL2

AL1

Inverter logic
circuit board

See I/O specs
on page

4–6

.

Dc

Load

Power

supply