B–26, Appendix b – Hitachi SJ200 Series User Manual

Page 240

Advertising
background image

ModBus Data Listing

Appendix B

B–26

A015

Pot./O–L input start
frequency enable

R/W Two options; select codes:

00... Use offset (A011 value)
01... Use 0 Hz

0038h

0, 1

A016

External frequency
filter time constant

R/W Range n = 1 to 8, where n =

number of samples for avg.

0039h

1 to 8

1

sample

A020

Multi-speed 0 setting

R/W Defines the first speed of a

multi-speed profile, range is
0.0 / start frequency to 400 Hz
A020 = Speed 0 (1st motor)

003Ah

0 / start

freq. to

4000

0.1 Hz

A220

Multi-speed 0 setting,
2nd motor

R/W Defines the first speed of a

multi-speed profile, range is
0.0 / start frequency to 400 Hz
A220 = Speed 0 (2nd motor)

003Bh

0 / start

freq. to

4000

0.1 Hz

A021

Multi-speed 1 setting

R/W

Defines 15 more speeds,

range is 0.0 / start frequency to

400 Hz.

A021= Speed 1...
A035 = Speed 15

003Ch

0 / start

freq. to

4000

0.1 Hz

A022

Multi-speed 2 setting

R/W

003Dh

A023

Multi-speed 3 setting

R/W

003Eh

A024

Multi-speed 4 setting

R/W

003Fh

A025

Multi-speed 5 setting

R/W

0040h

A026

Multi-speed 6 setting

R/W

0041h

A027

Multi-speed 7 setting

R/W

0042h

A028

Multi-speed 8 setting

R/W

0043h

A029

Multi-speed 9 setting

R/W

0044h

A030

Multi-speed 10 setting

R/W

0045h

A031

Multi-speed 11 setting

R/W

0046h

A032

Multi-speed 12 setting

R/W

0047h

A033

Multi-speed 13 setting

R/W

0048h

A034

Multi-speed 14 setting

R/W

0049h

A035

Multi-speed 15 setting

R/W

004Ah

A038

Jog frequency setting

R/W Defines limited speed for jog,

range is 0.00 / start frequency
to 9.99 Hz

004Bh

0 / start

freq. to

999

0.01 Hz

A039

Jog stop mode

R/W Define how end of jog stops

the motor; three options:
00... Free-run stop
01... Controlled deceleration
02... DC braking to stop

004Ch

0, 1, 2

Holding Registers for “A” Group Standard Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.

Advertising