Overload restriction – Hitachi SJ200 Series User Manual

Page 105

Advertising
background image

SJ200 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–33

Overload Restriction

If the inverter’s output current exceeds a
preset current level you specify during
acceleration or constant speed, the overload
restriction feature automatically reduces the
output frequency to restrict the overload.
This feature does not generate an alarm or
trip event. You can instruct the inverter to
apply overload restriction only during
constant speed, thus allowing higher
currents for acceleration. Or, you may use
the same threshold for both acceleration and
constant speed.

When the inverter detects an overload, it
must decelerate the motor to reduce the
current until it is less than the threshold.
You can choose the rate of deceleration that
the inverter uses to lower the output current.

Motor

Current

Output

frequency

t

t

Restriction area

0

0

B022

B023

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

B021 Overload restriction

operation mode

Select the operating mode
during overload conditions,
three options, option codes:
00... Disabled
01... Enabled for acceleration
and constant speed
02... Enabled for constant
speed only

01

01

OL Mode ON

B022 Overload restriction

setting

Sets the level for overload
restriction, between 20% and
150% of the rated current of
the inverter, setting resolution
is 1% of rated current

Rated current x

1.5

A

OL LVL 002.40A

B023 Deceleration rate at

overload restriction

Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution is 0.1.

1.0

30.0

sec.

OL Cnst 0001.0s

Advertising