ModBus Data Listing

Appendix B

B–34

B085

Country code for initial-
ization (not accessible
to ModBus)

Select default parameter values
for country on initialization.
Note: Write not allowed from
network.

009Bh

B086

Frequency scaling
conversion factor

R/W Specify a constant to scale the

displayed frequency for D007
monitor, range is 0.1 to 99.9

009Ch

1 to 999

0.1

B087

STOP key enable

R/W Select whether the STOP key

on the keypad is enabled, two
option codes:
00... enabled
01... disabled

009Dh

0, 1

B088

Restart mode after FRS

R/W Selects how the inverter

resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)

009Eh

0, 1

B090

Dynamic braking usage
ratio

R/W Selects the rate of use (in %) of

the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value

009Fh

0 =

disabled

, 1 to
1000

enabled

0.1 %

B091

Stop mode selection

R/W Selects how the inverter stops

the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)

00A0h

0, 1

B092

Cooling fan control

R/W Selects when the fan is ON per

inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature
controlled

00A1h

0, 1, 2

B095

Dynamic braking
control

R/W Three option codes:

00... Disable
01... Enable during RUN only
02... Enable always

00A2h

0, 1, 2

B096

Dynamic braking
activation level

R/W Range is:

330 to 380V (200V class),
660 to 760V (400V class)

00A3h

330 to

380, 660

to 760

1 V

“B” Group Fine Tuning Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.