Electronic Thermal Overload Alarm Setting

The thermal overload detection protects the
inverter and motor from overheating due to
an excessive load. It uses a current/inverse
time curve to determine the trip point.

First, use B013 to select the torque charac-
teristic that matches your load. This allows
the inverter to utilize the best thermal
overload characteristic for your application.

The torque developed in a motor is directly
proportional to the current in the windings,
which is also proportional to the heat generated (and temperature, over time). Therefore,

“B” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

B001 Selection of automatic

restart mode

Select inverter restart method,
four option codes:
00... Alarm output after trip,
no automatic restart
01... Restart at 0Hz
02... Resume operation after
frequency matching
03... Resume previous freq.
after freq. matching, then
decelerate to stop and display
trip info.

00

00

IPS POWR ALM

B002 Allowable under-

voltage power failure
time

The amount of time a power
input under-voltage can occur
without tripping the power
failure alarm. Range is 0.3 to
25 sec. If under-voltage exists
longer than this time, the
inverter trips, even if the restart
mode is selected.

1.0

1.0

sec.

IPS Time 0001.0s

B003 Retry wait time before

motor restart

Time delay after under-voltage
condition goes away, before
the inverter runs motor again.
Range is 0.3 to 100 seconds.

1.0

1.0

sec.

IPS Wait 0001.0s

B004 Instantaneous power

failure / under-voltage
trip alarm enable

Two option codes:
00... Disable
01... Enable

00

00

sec.

IPS TRIP OFF

B005 Number of restarts on

power failure / under-
voltage trip events

Two option codes:
00... Restart 16 times
01... Always restart

00

00

sec.

IPS RETRY 16

Output frequency

Constant torque

Reduced

torque

B013 = 01

B013 = 00

Torque

5

20

60

120

Hz

100%

80%

60%

0