H” group: motor constants functions, H” group: motor constants functions 3–55 – Hitachi SJ200 Series User Manual

Page 127

Advertising
background image

SJ200 Inverter

Conf

igur

ing

Dr
iv

e P

a

ra

m

e

ters

3–55

“H” Group: Motor Constants Functions

The “H” Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values to
match the motor. Parameters H006 and H007
are factory-set. If you want to reset the
parameters to the factory default settings, use
the procedure in

“Restoring Factory Default

Settings” on page 6–8

.

Other motor parameters are automatically
calculated and used when the inverter is in
intelligent sensorless vector control (iSLV)
mode. Use A044 to select the torque control algorithm as shown in the diagram. The
Sj200 inverter’s iSLV mode eliminates the need for manual entry of additional motor
parameters, or even for doing an auto-tuning procedure.

Output

Inverter Torque Control Algorithms

V/f control,

constant torque

V/f control,

variable torque

Intelligent sensor-

less vector control

(

i

SLV)

00

01

02

A044

“H” Function

Run

Mode

Edit

Defaults

Func.

Code

Name /

SRW Display

Description

–FEF

(EU)

–FU

(USA)

Units

H003 Motor capacity

Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11

Specified by

the capacity of

each inverter

model

kW

AUX K 0.4 kW

H203 Motor capacity, 2nd

setting

Nine selections:
0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7
5.5 / 7.5 / 11

kW

2AUXK 0.4 kW

H004 Motor poles setting

Four selections:
2 / 4 / 6 / 8

4

4

poles

AUX P 4p

H204 Motor poles setting, 2nd

motor

Four selections:
2 / 4 / 6 / 8

4

4

poles

2AUXP 4p

H006 Motor stabilization

constant

Motor constant (factory set),
range is 0 to 255

100

100

AUX KCD 100

H206 Motor stabilization

constant, 2nd motor

Motor constant (factory set),
range is 0 to 255

100

100

2AUXKCD 100

H007 Motor voltage select

Two selections, option codes:
00... 200V
01... 400V

Factory set

according to

inverter model

V

AUX Volt 200V

H207 Motor voltage select,

2nd motor

Two selections, option codes:
00... 200V
01... 400V

V

2AUXVolt 200V

Advertising