SJ200 Inverter

Appendix B

B–33

B021

Overload restriction
operation mode

R/W Select the operating mode

during overload conditions,
three options, option codes:
00... Disabled
01... Enabled for acceleration
and constant speed
02... Enabled for constant
speed only

0092h

0, 1, 2

B022

Overload restriction
setting

R/W Sets the level for overload

restriction, between 20% and
150% of the rated current of
the inverter, setting resolution
is 1% of rated current

0093h

2000 to

15000

0.01%

B023

Deceleration rate at
overload restriction

R/W Sets the deceleration rate when

inverter detects overload, range
is 0.1 to 30.0, resolution is 0.1

0094h

1 to 300

0.1 sec

B031

Software lock mode
selection

R/W Prevents parameter changes, in

four options, option codes:
00... all parameters except
B031 are locked when [SFT]
terminal is ON
01... all parameters except
B031 and output frequency
F001 when [SFT] terminal is
ON
02... all parameters except
B031 are locked
03... all parameters except
B031 and output frequency
F001 setting are locked

0095h

0, 1, 2, 3

B080

[AM] analog signal
gain

R/W Adjust of analog output at

terminal [AM],
range is 0 to 255

0096h

0 to 255

B082

Start frequency adjust-
ment

R/W Sets the starting frequency for

the inverter output, range is 0.5
to 9.9 Hz

0098h

5 to 99

0.1 Hz

B083

Carrier frequency
setting

R/W Sets the PWM carrier (internal

switching frequency), range is
2.0 to 14.0 kHz

0099h

20 to

140

0.1 Hz

B084

Initialization mode
(parameters or trip
history)

R/W Select the type of initialization

to occur, two option codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization

009Ah

0, 1, 2

“B” Group Fine Tuning Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.