B–38, Appendix b – Hitachi SJ200 Series User Manual

Page 252

Advertising
background image

ModBus Data Listing

Appendix B

B–38

C082

OI input span calibra-
tion

R/W Scale factor between the

external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%

00C8h

0 to 2000

0.1 %

C085

Thermistor input tuning

R/W Range is 0.0 to 200.0%

00EEh

0 to 2000

0.1 %

C086

[AM] terminal offset
tuning

R/W Range is 0.0 to 10.0V

00C9h

0 to 100

0.1 V

C091

Debug mode enable

Displays debug parameters.
Two option codes:
00... Disable
01... Enable

C101

Up/Down memory
mode
selection

R/W Controls speed setpoint for the

inverter after power cycle. Two
option codes:
00... Clear last frequency
(return to default frequency
F001)
01... Keep last frequency
adjusted by UP/DWN

00CFh

0, 1

C102

Reset selection

R/W Determines response to Reset

input [RST].
Three option codes:
00... Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01... Cancel trip state at signal
OFF transition, stops inverter if
in Run Mode
02... Cancel trip state at input
signal ON transition, no effect
if in Run Mode

00D0h

0, 1, 2

C141

Input A select for logic
output

R/W

See

“Output Logic and

Timing” on page 3–53

00EFh

0, 1, 2, 3,
4, 5, 6, 7,

8, 9

C142

Input B select for logic
output

R/W

00F0h

C143

Logic function select

R/W Applies a logic function to

calculate [LOG] output state,
three options:
00... [LOG] = A AND B
01... [LOG] = A OR B
02... [LOG] = A XOR B

00F1h

0, 1, 2

C144

Terminal [11] ON delay R/W Range is 0.0 to 100.0 sec.

00F2h

0 to 1000

0.1 sec

C145

Terminal [11] OFF
delay

R/W Range is 0.0 to 100.0 sec.

00F3h

0 to 1000

0.1 sec

“C” Group Intelligent Terminal Functions

Func.

Code

Name

R/W

Description

Network Data

Reg.

Range

Res.