Add frequency enable – Hitachi SJ200 Series User Manual

Page 159

Advertising
background image

Using Intelligent Input Terminals

Oper

ations

and Monitor

ing

4–32

ADD Frequency Enable

The inverter can add or subtract an offset value to the output frequency setting which is
specified by A001 (will work with any of the five possible sources). The ADD
Frequency is a value you can store in parameter A145. The ADD Frequency is summed
with or subtracted from the output frequency setting only when the [ADD] terminal is
ON. Function A146 selects whether to add or subtract. By configuring an intelligent
input as the [ADD] terminal, your application can selectively apply the fixed value in
A145 to offset (positively or negatively) the inverter output frequency in real time.

A001

Function F001 setting

Control terminal

ModBus network input

Calculate function output

Keypad potentiometer

A145

+

+/–

ADD frequency

Frequency source setting

Output frequency setting

[ADD]

Intelligent input

A146 ADD direction select

Option

Code

Terminal

Symbol

Function Name

Input

State

Description

50

ADD

ADD Frequency
Enable

ON

Applies the A145 Add Frequency value to the
output frequency.

OFF

Does not apply the Add Frequency. The output
frequency retains its normal value.

Valid for inputs:

C001, C002, C003, C004,
C005, C006

Required settings:

A001, A145, A146

Notes:

A001 may specify any source; the Add Frequency
will be added to or subtracted from that value to
yield the output frequency value.

1

2

3

4

5

6

L

PCS

Example (requires input configuration—see
page

3–41

):

See I/O specs on page

4–6

.

ADD

Advertising