3 power supply, 4 connectors, 3 power supply 2.4 connectors – GE Industrial Solutions 6KCV300DVN User Manual

Page 13

Advertising
background image

6KCV300DVN

2

13

——————

HARDWARE DESCRIPTION

——————

Switch 8 Switch 7 Baud Rate

OFF

OFF

125 kBaud

OFF

ON

250 kBaud

ON

OFF

500 kBaud

ON

ON

125 KBaud

DN21

5.

The dip switch S1 determines the Slave address. The address “0” is reserved
to the Master and it must not be used. The switches S1 -7 and S1-8 do not
determine any address. The address is detected only when the board is
switched on. If the address is modified, the Drive has to be switched off
and then switched on in order to assume the new address.

6.

Connect the Bus cable to the BUS connection terminal.

7.

Switch on the drive.

8.

The LEDS PWR and RUN light up.

9.

Switch the Device Net power supply on; the LED H1 lights up.

10. The LED OP lights up when the Master/Slave connection has been

established.

2.3 POWER SUPPLY

The power supply is provided by the XO connector, which is used to connect
the data between the 6KCV300DVN board and the Drive regulation board.

Absorbed current: 350 mA

2.4 CONNECTORS

Connector

:

It allows to connect the ground (GNDE) of the
external power supply to the ground (PE).

Connector XS

It allows to connect the ground (PE) to the
DeviceNet cable shield.

Terminal BUS

See the figure below. It allows to connect the
6KCV300DVN board to the DeviceNet network.
The pins are the following:

Advertising