For error codes see chapter 6.0 – GE Industrial Solutions 6KCV300DVN User Manual

Page 56

Advertising
background image

GEI-100431

————

SETTING VIRTUAL DIGITAL I/Os

————

5

56

5.2.6.1.1 Write Single Virtual Digital Output configuration

The data frame of the writing of the single configuration of the “Virtual Digital
Outputs” is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

10hex

Set_Attribute_Single -

Common Service.

Class ID

6Bhex

Virtual Digit Output

Configuration Class Object

Instance ID

01

Virtual Digit Output

Instance ID

Byte

Attribute ID

XX

Virtual Digit Output

involved in the configuration

Word

Virtual Digit Input

Word XX

XXXX

2)

Drive parameter index
assigned to the Virtual

Digital Output XX word

dn5120

See Note

1)

1)

Byte or Word depending on the type of allocation executed by the Master.

2)

The format of the Drive parameter index is Low Byte - High byte.

5.2.6.1.2 Write Single Virtual Digital Output Configuration - Reply OK

If the single configuration of the “Virtual Digital Outputs” is written correctly,
the response is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

10hex OR

80hex

Set_Single - Attribute Reply

code - Common Service.

General

Error

00

Additional

00

dn4040

Byte

Zero means service correctly

executed

5.2.6.1.3 Write Single Virtual Digital Output configuration - Reply Error

If the writing of the single configuration of the “Virtual Digital Outputs” is
rejected, the response is the following:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

14hex OR

80hex

Set _Attribute_Single Reply

code- Common Service.

1Fhex

Error vendor specific (see

Additional field)

<> 1Fhex

DeviceNet specific error

code (see DeviceNet

Specifications).

Additional

XX

1)

Drive specific error code.

dn4050

Byte

General

Error

1)

For error codes see chapter 6.0.

Advertising