5 dip switches, 6 leds, 5 dip switches 2.6 leds – GE Industrial Solutions 6KCV300DVN User Manual
Page 14
GEI-100431
——————
HARDWARE DESCRIPTION
——————
2
14
Pin
Signal
Description
1 CAN_GND
Ground / 0V /V-
2
CAN_L
Can_L bus line (dominant low)
3 CAN_SHLD
CAN shield
4
CAN_H CAN_H bus line (dominant high)
5
CAN_V+
CAN external positive supply
(dedicated for supply of
transceiver and optocouplers)
dn22
2.5 DIP SWITCHES
S3 Interrupt selection from selector S5 (INT1/INT2) to the microcontroller
8032 or to the interrupt input of the dual port ram (INTR). Default position
is A (interrupt to the dual port ram).
S4 Synchronisation connection for the reset signal of the 6KCV300DVN
board to the connected regulation board. Default position is ON.
S5 It is used to connect the signal INT_OPZ to the signal INT1 (S5.B) or to
the signal INT2 (S5.A). The interface board is standard set as OPTION 1,
therefore INT_OPZ is connected to the signal INT1. (Default position is
A).
S6 It is used to connect the signal OUT_OPZ to the signal OUT1 (S6.A) or
OUT2 (S6.B). Default position is B.
S7 It is used to connect the signal CEM_OPZ to the signal OPZ1 (S7.B) or to
the signal OPZ2 (S7.A). The 6KCV300DVN board is standard set as
OPTION 1, therefore CEM_OPZ is connected to the signal OPZ1. Default
position is B.
S8 Connection of the dual port ram BUSY signal to the signal RDY_EXT.
Default position is ON.
2.6 LEDS
PWR +5V power supply.
RST
Reset active.
H1
+5V power supply on the RS 485 driver side. It is supplied by the Bus.
RUN It is on when the microcontroller is operating.
OP
It is on when the Master/Slave connection is established.