SETTING VIRTUAL DIGITAL I/Os

————

5

58

5.2.6.2 Read Virtual Digital Output configuration

In this example is shown the reading of the configuration of the “Virtual Digital
Outputs”; the cases of positive and wrong reading are distinguished.

5.2.6.2.1 Read Single Virtual Digital Output configuration

The data frame for the reading of the single configuration of the “Virtual Digital
Outputs” is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

0Ehex

Get_Attribute_Single - Common

Service

Class ID

6Bhex

Virtual Digit I/O Configuration

Class Object

Instance ID

01

Virtual Digit Output Instance

ID

Byte

Attribute ID

XX

Virtual Digit Output XX word

involved in the configuration

dn5140

See Note

1)

1)

Byte or Word depending on the type of allocation executed by the Master.

5.2.6.2.2 Read Single Virtual Digital Output configuration - Reply OK

If the single configuration of the “Virtual Digital Outputs” is read correctly,
the response is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

0Ehex OR

80hex

Get_Attribute_Single Reply code-

Common Service

Word

Word 0 Virtual

Digital Output XXXX

1)

Drive parameter index assigned to

the Virtual Digital Output XX word

dn5150

1)

The format of the Drive parameter index is Low Byte - High byte.