5.2.6.2.3 Read Single Virtual Digital Output configuration - Reply Error

If the reading of the single configuration of the “Virtual Digital Outputs” is
rejected, the response is the following:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

14hex OR

80hex

Get _Attribute_Single Reply

code- Common Service.

1Fhex

Error vendor specific (see

Additional field)

<> 1Fhex

DeviceNet specific error

code (see DeviceNet

Specifications).

Additional

XX

1)

Drive specific error code.

dn4105

Byte

General

Error

1)

For error codes see chapter 6.0.

5.2.6.2.4 Read Entire Virtual Digital Output configuration

The data frame for the reading of the entire configuration of the “Virtual Digital
Outputs” is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

01hex

Get_Attribute_All - Common

Service

Class ID

6Bhex

Virtual Digital Output

Configuration Class Object

Instance ID

01

Virtual Digital Output Instance

ID

dn5160

See Note

1)

1)

Byte or Words depending on the type of allocation executed by the Master.

5.2.6.2.5 Read Entire Virtual Digital Output configuration - Reply OK

If the entire configuration of the “Virtual Digital Outputs” is read correctly,
the response is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

01hex OR

80hex

Get_Attribute_All Reply code-

Common Service

Word 0 Virtual

Digital Output

Drive parameter index assigned to the

Virtual Digital Output first word.

Word xx Virtual

Digital Output

Drive parameter index assigned to the

Virtual Digital Output xxth word.

Word 15 Virtual

Digital Output

Drive parameter index assigned to the

Virtual Digital Output 16th word.

dn5170

Word

XXXX

1)

1)

The format of the Drive parameter index is Low Byte - High byte.