3 write dgf parameter - reply error, 2 read dgf parameter, 1 read dgf parameter request – GE Industrial Solutions 6KCV300DVN User Manual

Page 28

Advertising
background image

GEI-100431

——————

BYTE ASSIGNMENT

——————

3

28

3.2.2.6.1.3 Write DGF parameter - Reply Error

If the writing of the DGF parameter is rejected, the response is:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service

Code

33hex OR

80hex

Set DGF Parameter

Reply code- Object

Specific Service

Word

Result

XXXX

1)

DGF specific error code

dn3975ge

1) For error codes see DGF-manual.

3.2.1.6.2 Read DGF parameter

In this example the reading of a DGF-parameter is shown; the cases of positive
or wrong reading are distinguished.

3.2.1.6.2.1 Read DGF Parameter Request

The data frame for the reading of a DGF parameter is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service

Code

32hex

Get DGF Parameter -

Object Specific Service

See Note

1)

Class ID

67hex

DGF Parameter Access

Class Object

Word

Instance

ID

XXXX

DGF Parameter Index in

format Low byte-High

byte

Byte

Data Type

2)

XX

DGF specific data type

code

Byte

N/U

0

Not used; has to be set to

zero

dn3980ge

1) Byte or Word depending on the type of allocation executed by the Master.

2) For data-type codes see DGF-manual.