6 behavior, 1 write virtual digital input configuration, 1 write single virtual digital input configuration – GE Industrial Solutions 6KCV300DVN User Manual

Page 49

Advertising
background image

6KCV300DVN

5

49

————

SETTING VIRTUAL DIGITAL I/Os

————

5.1.6 Behavior

This object allows the assignment of Drive parameters to the “Virtual Digital
Inputs” so that the Master can write cyclically the values of these parameters.
The assignment of the Drive parameter is accomplished through the parameter
index; if the parameter for any reason cannot be assigned to a “Virtual Digital
Input”, an error code will be returned.

5.1.6.1 Write Virtual Digital Input configuration

In this example is shown the writing of the configuraton of the “Virtual Digital
Inputs”; the cases of positive and wrong writing are distinguished.

5.1.6.1.1 Write Single Virtual Digital Input Configuration

The data frame for the writing of the single configuration of the “Virtual Digital
Inputs” is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

10hex

Set_Attribute_Single -

Common Service.

Class ID

6Ahex

Virtual Digit Input

Configuration Class Object

Instance ID

01

Virtual Digit Input Instance

ID

Byte

Attribute ID

XX

Virtual Digit Input involved

in the configuration

Word

Virtual Digit Input

Word XX

XXXX

2)

Drive parameter index
assigned to the Virtual

Digital Input XX word

dn5030

See Note

1)

1)

Byte or Word depending on the type of allocation executed by the Master.

2)

The format of the Drive parameter index is Low Byte - High byte.

5.1.6.1.2 Write Single Virtual Digital Input configuration - Reply OK

If the single configuration of the “Virtual Digital Inputs” is written correctly,
the response is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

10hex OR

80hex

Set_Single - Attribute Reply

code - Common Service.

General

Error

00

Additional

00

dn4040

Byte

Zero means service correctly

executed

Advertising