3 defining object interface, 4 i/o assembly instances, 5 i/o assembly data attributes format – GE Industrial Solutions 6KCV300DVN User Manual
Page 20
GEI-100431
——————
BYTE ASSIGNMENT
——————
3
20
3.1.3 Defining object interface
The object interface of the 6KCV300DVN board is the following:
Object
Interface
Identity
Message router
Message Router
Explicit Messaging
Connection Instance
DeviceNet
Message router
Connection
Message router
Assembly
I/O Connection or
Message Router
Drive Parameter Access
Message router
DGF Parameter Access
Message router
Poll Slave->Master CFG
Message router
Poll Master->Slave CFG
Message router
Virtual Digital Input CFG
Message router
Virtual Digital Output CFG
Message router
dn313ge
3.1.4 I/O assembly instances
The following table identifies the “I/O Assembly” instances of the
6KCV300DVN board:
Number Type
Name
195
Input PMSCS Assembly Cons
194
Output PMSCS Assembly Prod
DN325
3.1.5 I/O assembly data attributes format
The “I/O Assembly” attributes format for the Input is the following:
PMSCS Assembly Cons:
Instance
Byte
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
2
….
….
(n2)-1
n*2
dn330
….
word #n to consume, low byte
word #n to consume, high byte
195
word #1 to consume, low byte
word #1 to consume, high byte
word #2 to consume, low byte
….
(n) is the number of consumed Words; it is 4 (8bytes).
PMSCS Assembly Prod: