1 devicenet error types – GE Industrial Solutions 6KCV300DVN User Manual
Page 74
GEI-100431
———— KEYBOARD INTERFACE ———
7
74
7.7.3.1 DeviceNet error types
DNetStatus
Meaning
Code
0
No error exists
1
Resource not available
2
Value out of range
3
transportClass_trigger invalid
4
Invalid service for object state
5
Illegal message format
6
Invalid condition for transmission
7
Outstanding request exists
8
Object does not exist
9
Service not supported
10
Duplicate MacId check response received
11
Duplicate MacId check request received
12
Object not available
13
OpenAllIOCnxn failed
14
Duplicate MacId error
15
Time-out error
16
Software error
17
Message error
18
Hardware error
DnetStAux
Meaning
Code
0
No additional information
1
All available group 2 message identifiers have been allocated
2
Invalid Ainitial_comm_characteristic@ attribute
3
All available group 1 message identifiers have been allocated
4
All available group 3 message identifiers have been allocated
5
Invalid value within the AtransportClass_trigger@ attribute
6
An Apply request is sent to a Connection instance when it is in
the Established or Timed-out state
7
Illegal to send fragmented explicit Connection message
8
Connection object must be in Established state and must beMessaging
type of Connection in order to send a cnxn-based request
9
Cannot send cnxn-based request since a request is outstanding
10
Invalid instance identifier specified in received explicit message
request
11
Explicit message request is directed at non-existent cnxn instance
12
A Create request can only be sent to the class, not a particular
instance
13
ConfigCnxnndex already set
14
Unable to create cnxn class
15
Apply_attribute cannot be sent to the cnxn class, only a specific
instance
16
Invalid service code received in explicit message request
17
Class specified in received Cnxn Based Explicit request message
does not exist
18
More than 2 group 2 object have been created