2 configuration object virtual digital output, 1 class code, 2 class attributes – GE Industrial Solutions 6KCV300DVN User Manual

Page 54: 3 instance attributes

Advertising
background image

GEI-100431

————

SETTING VIRTUAL DIGITAL I/Os

————

5

54

5.2 CONFIGURATION OBJECT VIRTUAL DIGITAL OUTPUT

For the assignment of Drive parameters to the 16 Words of the Virtual Digital
Outputs a new object with a specific identifier class is used.

The object is made as follows:

Class ID: 6Bh.

Class Attribute:

Revision

Instance Attribute:

·

ID = 1: Word for configuration first Output (direction Master ->Slave).

·

ID = 2: Word for configuration second Output (direction Master->Slave).

·

ID = x: Word for configuration Outputs (direction Master->Slave).

·

ID = 16; Word for configuration sixteenth Output (direction Master->Sla-
ve).

5.2.1 Class code

Class Code: 6Bhex

5.2.2 Class attributes

Number

Need in

implementation

Access Rule

Name DeviceNet

Data Type

Description

of Attribute

Semantics of

values

1

Optional

Get

Revision

UINT

Revision of

this object

dn345

5.2.3 Instance attributes

Number

Need in

implementation

Access Rule

Name DeviceNet

Data Type

1

X

16

dn5100

Description of Attribute

Drive parameter assigned to

the first Virtual Digital

Output

Drive parameter assigned to

the Xth Virtual Digital

Output

Drive parameter assigned to

the 16th Virtual Digital

Output

Required

Set

DGT

Out

Conf.

UINT