GEI-100431
——————
POLLING FUNCTION
——————
4
42
4.2.6.1.4 Write Entire Polling M->S configuration
The data frame for writing the entire configuration of the Polling M->S is
composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Byte
Service Code
02hex
Set_Attribute_All -Common
Service.
Class ID
69hex
Polling S->M Configuration
Class Object.
Instance ID
01
Polling S->M Instance ID.
Word 0 Polling
M->S
Drive parameter index assigned
to the Polling M->S first word.
Word xx Polling
M->S
Drive parameter index assigned
to the Polling M->S xx th word.
Word 4 Polling
M->S
Drive parameter index assigned
to the Polling M->S 4th word.
dn4180
See Note
1)
Word
XXXX
2)
1)
Byte or Word depending on the type of allocation executed by the Master.
2)
The format of the Drive parameter index is Low Byte - High Byte.
4.2.6.1.5 Write Entire Polling M->S configuration - Reply OK
If the entire configuration of the Polling M->S is written correctly, the response
is composed as follows:
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
02hex OR
80hex
Set_Attribute_All Reply
code- Common Service.
General
Error
00
Additional
00
dn4070
Byte
Zero means service correctly
executed.
4.2.6.1.6 Write Entire Polling M->S configuration - Reply Error
If the writing of the entire configuration of the Polling M->S is rejected, the
response is the following:
DATA TYPE
FIELD
VALUE
MEANING
Service
Code
14hex OR 80hex
Set _Attribute_ All Reply code-
Common Service
1Fhex
Error vendor specific (see
Additional field)
<> 1Fhex
DeviceNet specific error code
(see DeviceNet Specifications)
Additional
XX
1)
Drive specific error code.
dn4080
Byte
General
Error
1)
For error codes see chapter 6.0.