For error codes see chapter 6.0 – GE Industrial Solutions 6KCV300DVN User Manual

Page 41

Advertising
background image

6KCV300DVN

4

41

——————

POLLING FUNCTION

——————

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

10hex

Set_Attribute_Single -

Common Service.

Class ID

69hex

Polling M ->S Configuration

Class Object

Instance ID

01

Polling M ->S Instance ID

Byte

VALUE

XX

Polling M ->S word involved

in the configuration

Word

Word XX Polling

S->M

XXXX

2)

Drive parameter index

assigned to the Polling

M ->S XX word

dn4170

See Note

1)

1)

Byte or Word depending on the type of allocation executed by the Master.

2)

The format of the Drive parameter index is Low Byte - High byte.

4.2.6.1.2 Write Single Polling M->S configuration - Reply OK

If the single configuration of the Polling M->S is written correctly, the response
is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

10hex OR

80hex

Set_Single - Attribute Reply

code - Common Service.

General

Error

00

Additional

00

dn4040

Byte

Zero means service correctly

executed

4.2.6.1.3 Write Single Polling M->S configuration - Reply Error

If the writing of the single configuration of the Polling M->S is rejected, the
response is the following:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

14hex OR

80hex

Set _Attribute_Single Reply

code- Common Service.

1Fhex

Error vendor specific (see

Additional field)

<> 1Fhex

DeviceNet specific error

code (see DeviceNet

Specifications).

Additional

XX

1)

Drive specific error code.

dn4050

Byte

General

Error

1)

For error codes see chapter 6.0.