GEI-100431

——————

POLLING FUNCTION

——————

4

36

4.1.6.2 Read S->M Polling configuration

In this example is shown the reading of the configuration of the Polling S->M;
the cases of positive and wrong reading are distinguished.

4.1.6.2.1 Read Single Polling S->M configuration

The data frame for the reading of the single configuration of the Polling S->M
is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

0Ehex

Get_Attribute_Single -

Common Service

Class ID

68hex

Polling S ->M Configuration

Class Object

Instance ID

01

Polling S ->M Instance ID

Byte

Attribute ID

XX

Polling S ->M word involved

in configuration

dn4090

See Note

1)

1)

Byte or Word depending on the type of allocation executed by the Master.

4.1.6.2.2 Read Single Polling S->M configuration - Reply OK

If the single configuration of the Polling S->M is read correctly, the response
is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

0Ehex OR

80hex

Get_Attribute_Single Reply

code- Common Service.

Word

Word XX

Polling S->M XXXX

1)

Drive parameter index assigned

to the Polling S->M XX word.

dn4100

1)

The format of the Drive parameter index is Low Byte - High byte.