4 read entire polling s->m configuration, For error codes see chapter 6.0 – GE Industrial Solutions 6KCV300DVN User Manual

Page 37

Advertising
background image

6KCV300DVN

4

37

——————

POLLING FUNCTION

——————

4.1.6.2.3 Read Single Polling S->M configuration - Reply Error

If the reading of the single configuration of the Polling S->M is rejected, the
response is the following:

DATA TYPE

FIELD

VALUE

MEANING

Service

Code

14hex OR

80hex

Get _Attribute_Single Reply

code- Common Service.

1Fhex

Error vendor specific (see

Additional field)

<> 1Fhex

DeviceNet specific error

code (see DeviceNet

Specifications).

Additional

XX

1)

Drive specific error code.

dn4105

Byte

General

Error

1)

For error codes see chapter 6.0.

4.1.6.2.4 Read Entire Polling S->M configuration

The data frame for the reading of the entire configuration of the Polling S->M
is composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

01hex

Get_Attribute_All -Common

Service.

Class ID

68hex

Polling S->M Configuration

Class Object.

Instance ID

01

Polling S->M Instance ID.

dn4110

See Note

1)

1)

Byte or Word depending on the type of allocation executed by the Master.

4.1.6.2.5 Read Entire Polling S->M configuration - Reply OK

If the entire configuration of the Polling S->M is read correctly, the response is
composed as follows:

DATA TYPE

FIELD

VALUE

MEANING

Byte

Service Code

01hex OR

80hex

Get_Attribute_All -Common

Service.

Word 0 Polling

S->M

Drive parameter index assigned

to the Polling S->M first word.

Word xx

Polling S->M

Drive parameter index assigned
to the Polling S->M xx th word.

Word 4 Polling

S->M

Drive parameter index assigned

to the Polling S->M 4th word.

dn4120

Word

XXXX

1)

1)

The format of the Drive parameter index is Low Byte - High byte.

Advertising