Figure 530-1, Table 530-1, Dlp-530 – ADC Soneplex Broadband System User Manual

Page 120

Advertising
background image

ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

2-97

© 2000, ADC Telecommunications, Inc.

DLP-530

Page 2 of 3

8110-C

ODS2 CONFIGURATION

Group: 3

Unit Equip State : EQUIPPED T2 Service State : IS

Unit Service State: IS BER Alarm Thresh: 1E-8

Unit Protect State: UNPROTECTED BER Switch Thresh: 1E-6

T1 Service Line

PARAMETERS Provision State Code Circuit ID

========= ======= ==== ====================

T1 #1: YES OOS AMI

T1 #2: YES OOS AMI

T1 #3: YES OOS AMI

T1 #4: YES OOS AMI

T1 Remote Pulse Remote Remote PPS

PARAMETERS Equalization Frame Format Threshold

=========== ============ =============

T1 #1: N/A N/A N/A

T1 #2: N/A N/A N/A

T1 #3: N/A N/A N/A

T1 #4: N/A N/A N/A

Remote Housekeeping Labels:

Working Card HSKP1: RMT-HSKP1 HSKP2: RMT-HSKP2

Protect Card HSKP1: N/A HSKP2: N/A

Press CONTROL-A For Assistance

Figure 530-1. ODS2 Configuration Screen

Table 530-1. ODS2 Configuration Fields

FIELD

TYPE

OPTIONS

DESCRIPTION

DEFAULT

Group

Toggle

1, 2, 3, 4, 5, 6, or 7

Specifies the module’s group number
designated on the chassis.

1

Unit Equipment
State

Toggle

Equipped

Establishes communication with MPU. Module
must be set to EQUIPPED before remaining
selections are allowed. Sets all other fields to
default values and allows MPU to process
equipment alarms.

UNEQUIPPED

UNEQUIPPED

No communication with MPU.

Unit Service State

Toggle

IS (In-Service)

Places the unit in service and allows equipment

alarm reporting by the MPU. Must be set to IS
for reporting of equipment alarms.

OOS

OOS (Out-Of-Service)

Removes unit from service and stops equipment

alarm reporting by the MPU.

Unit Protect State

Toggle

PROTECTED

Designates that equipment APS is available.

UNPROTECTED

UNPROTECTED

Designates that equipment APS is not available.

(continued)