ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

2-187

© 2000, ADC Telecommunications, Inc.

DLP-558

Page 2 of 3

4. Repeat Step 3 for each field that you wish to change.

5. Assign the selections by pressing Enter or Return.

6. Momentarily press RESET on the MPU front panel, or perform a soft reset, in order to re-

initialize the X.25 configurations.

Reference:

DLP-519

MPU Replacement and Testing

Reference:

DLP-538

Reset/LED Test Commands

Stop! You have completed this procedure.

Table 558-1. Data Link Layer LAPB Parameters

DATA LINK PARAMETER

SET

VALUE

RANGE

CONFIGURABLE

DEFAULT

Address Field Assignment *

DTE, DCE (A=1, B=3)

DTE (A=3, B=1)

Modulo

8

Window Size (K) *

1 to 7 frames

7

Frame Size (Bits per I frame) *

1080, 2104 bits

2104

N2 (retransmission count) *

2 - 16

7

T1 (retry timer) *

2 to 20 seconds

3 seconds

T2 (response delay timer)

0.3 seconds

T3 (not supported)

T4 (not supported)

* These are user-programmable parameters through the Craft Interface.

Table 558-2. Virtual Circuit Default Assignments

VIRTUAL

CIRCUIT

CIRCUIT

TYPE

LOGICAL

CHANNEL #

APPLICATION

1

PVC

1

TL1

2

PVC

2

Craft

3

SVC

N/A

N/A

Note

: Autonomous messages are always sent except when

inhibited by the TL1 INH-MSG command.