ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

2-13

© 2000, ADC Telecommunications, Inc.

NTP-003

Page 2 of 2

Do Items Below in the Order Listed

For Details Go To

5. Momentarily press the LMPTST switch on the APU front panel

and verify that all indicators light.

6. Connect terminal equipment to Craft port on the front of the MPU.

DLP-504

7. Log on to the Craft Interface.

DLP-526

8. Clear Alarm History.

DLP-527

9. Enter Target Identifier and set date and time now or during

provisioning (the turn-up process).

DLP-528

10. Configure DS3 MUX as required.

DLP-529

11. Configure ODS2 modules as required.

DLP-530

12. Clean and mate fiber optic connectors and adapters as required.

DLP-507

13. Connect the test equipment at both ends of the system and perform

an end-to-end test between the Soneplex chassis and the remote
module.

DLP-510

14. If the Soneplex system being tested is equipped with protection

modules:

Execute Force/APS commands through the Craft Interface.

DLP-537

Perform Manual (Force) Switch to Protect test on DS3 MUX
module.

DLP-511

Perform APS test on DS3 MUX module.

DLP-512

Perform Manual (Force) Switch to Protect Test on ODS2 module.

DLP-513

Perform APS test on ODS2 module.

DLP-514

15. Log off from the Craft Interface system.

DLP-564

16. Complete assignment forms and update office records as required by

local procedures.

DLP-523