Ods2 module alarm level setting, Dlp-561 – ADC Soneplex Broadband System User Manual

Page 216

Advertising
background image

ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance

2-193

© 2000, ADC Telecommunications, Inc.

DLP-561

Page 1 of 3

ODS2 MODULE ALARM LEVEL SETTING

Summary:

This procedure provides instructions for setting ODS2 Alarm Levels.

Note:

A “toggle” field type means the user can press the space bar to view and select the

next option that is described; or the user can press the “R” key to view and select the
previous option. An “input” field type means the user must type an entry in the field
according to the parameters described. A “fixed” field is locked, and cannot be changed by
the user.

Note:

Edits can be made in the configuration database in one of two ways: 1) If the

complete field is highlighted, use the space bar to toggle forward or the “R” key to
reverse toggle through the options for that field. 2) If only the first space or the field is
highlighted, type in the data that applies to that field.

Note:

Edits to the configuration database can be saved after each change in one of two

ways: 1) Press an arrow key and then Enter or Return once; or 2) Press Enter or Return
twice

after all selections and entries are made in the screen but before leaving the screen.

If the entries have been accepted, a message “Configuration Successful…
Press Any Key To Continue” appears on the screen.

Note:

Press CONTROL-A for help information on moving around and editing fields.

1. Use the arrow keys to select Alarms from the Main Menu. Press Enter or Return.

2. Use the arrow keys to select Set Alarm Levels from the Alarms menu. Press Enter or

Return.

3. Select Set ODS2 Alarm Levels from the Set Alarm Levels Menu. Press Enter or Return. An

ODS2 Alarm Levels screen is shown in

Figure 561-1

.

4. Move to the Group toggle field. Select group number 1, 2, 3, 4, 5, 6, or 7.

Reference:

TAD-106

Access Identifier

5. Move to the Equipment Alarms toggle fields. Select CRITICAL (CR), MAJOR (MJ),

MINOR (MN), EVENT (EV) or NOT RPTD (not reported) for each field that you wish to
change.

Note:

Abbreviations of the alarm field options (except NOT RPTD) will appear in the

Active Alarms and Alarm History screens. In addition, what options you select at any
alarm level setting screen will determine whether you will be notified of the alarm.

Reference:

DLP-552

Alarm/Event Notification Level Setting

6. Move to the DS2 Facility Alarms toggle fields. Select CRITICAL, MAJOR, MINOR,

EVENT, or NOT RPTD for each field that you wish to change.

Advertising