Run mode, Recoverable error mode, Unrecoverable error mode – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 113

Advertising
background image

114

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 11 Troubleshooting

If the power-up or reset is successful, the current monitoring relay will enter

Run

Mode.

Run Mode

In Run Mode, the EC4 Current Monitoring Relay will operate as a slave device to
a master device. The

NETWORK STATUS LED will blink green if there are no

network connections established with a network master. When one or more
connections are in the “established” state, the

NETWORK STATUS LED will

turn solid green. When one or more connections are in the “timed-out” state, the
NETWORK STATUS LED will blink red. In the Run Mode, the EC4 Current
Monitoring Relay will:

1.

Accept messages from a master on the DeviceNet network

2.

Send response messages, COS messages, or CYCLIC messages to a master.

If a communication error is detected, the EC4 Current Monitoring Relay will
either enter the

Recoverable Error or Unrecoverable Error Mode.

Recoverable Error Mode

In Recoverable Error Mode, the EC4 Current Monitoring Relay’s

NETWORK

STATUS LED turns solid red. The current monitoring relays will respond to
messages that are specified in offline node recovery message protocol.

Unrecoverable Error Mode

In Unrecoverable Error Mode, the EC4 Current Monitoring Relay’s
NETWORK STATUS LED turns solid red. The current monitoring relay
continues in this state as long as the device is powered.

Error Type

Description

LED State

Recoverable

Duplicate node address detected

Solid Red

Error Type

Description

LED State

Unrecoverable

Power-up initialization failure

Solid Red

Incorrect baud rate

Fatal communication error (bus-off)