Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 141

Advertising
background image

142

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Appendix B DeviceNet Information

115

Get

Warning Status

WORD

Bit 0 = Reserved
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault **
Bit 4 = Reserved
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = Reserved
Bit 12 = Config Fault
Bit 13 = PM Starts
Bit 14 = PM Oper Hours

116

Get

Trip Log 0

WORD

Last trip condition. Bit definitions of the
value are the same as attribute 114

117

Get

Trip Log 1

WORD

Last trip condition. Bit definitions of the
value are the same as attribute 114

118

Get

Trip Log 2

WORD

Last trip condition. Bit definitions of the
value are the same as attribute 114

119

Get

Trip Log 3

WORD

Last trip condition. Bit definitions of the
value are the same as attribute 114

120

Get

Trip Log 4

WORD

Last trip condition. Bit definitions of the
value are the same as attribute 114

121

Get

Device Status

WORD

Bit 0 = Trip
Bit 1 = Warning
Bit 2 = OutputA
Bit 3 = OutputB
Bit 4 = Input 1
Bit 5 = Input 2
Bit 6 = Input 3
Bit 7 = Input 4
Bit 8 = Motor Current
Bit 9 = GF Current

124

Get/Set

Trip Enable

WORD

Bit 0 = Reserved
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault **
Bit 4 = Stall
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = Reserved
Bit 12 = Reserved
Bit 13 = Reserved
Bit 14 = Remote Trip
Bit 15 = Start Inhibit

125

Get/Set

Warning Eanble

WORD

Bit 0 = Reserved
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault **
Bit 4 = Stall
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = Reserved
Bit 12 = Device Config
Bit 13 = PM Starts
Bit 14 = PM Oper Hours

Table 58 - Control Supervisor Object Instance Attributes