Protective Trip and Warning Functions Chapter 3

Overcurrent Warning

The EC4 Current Monitoring Relay will issue a warning with an overcurrent
condition if:

• The current in any of the phases exceeds the current specified for the

corresponding OC Warn Level parameter (Parameter 120 for L1,
parameter 123 for L2, & parameter 126 for L3)

• No warning condition already exists

If an overcurrent warning parameter is satisfied, the following will occur:

• The TRIP/WARN LED will flash a yellow blinking pattern depending on

which phase encountered the overcurrent warning condition

5 blinks for L1 overcurrent

6 blinks for L2 overcurrent

7 blinks for L3 overcurrent

• Parameter 15, Warning Status, will change

Bit 4 will go to "1" for L1 overcurrent

Bit 5 will go to "1" for L2 overcurrent

Bit 6 will go to "1" for L3 overcurrent

• Bit _ in Parameter 21, Device Status, will go to "1"

Overcurrent Trip

The EC4 Current Monitoring Relay will trip with an overcurrent indication if:

• The current in any of the phases exceeds the current specified for the

corresponding OC Trip Level parameter (Parameter 118 for L1, parameter
121 for L2, & parameter 124 for L3)

• No trip currently exists

If the EC4 Current Monitoring Relay trips on an overcurrent condition, the
following will occur:

Table 11 - Overcurrent Setting Ranges

Current Range [A]

Min. [A]

Max. [A]

Default [A]

0.4…2

0.4

2.5

0.4

1…5

1

6.25

1

3…15

3

18.75

3

5…25

5

31.25

5

9…45

9

56.25

9

18…90

18

112.5

18

9…5000

9

6250

9