Protective Trip and Warning Functions Chapter 3

Starts Counter parameter is equal to or greater than the value set in the PM

- # Starts parameter

Upon a

PM - # Starts warning, the following will occur:

• The TRIP/WARN LED will flash an amber 14-blink pattern
• Bit 13 in Parameter 15, Warning Status, will go to “1”
• Bit 1 in Parameter 21, Device Status, will go to “1”

Parameter 101,

PM - # Starts, allows the installer to set a number of starts. It is

adjustable from 0…65,535.

The EC4 Current Monitoring Relay will give a

PM – Oper. Hours warning

indication when:

PM – Oper. Hours warning is enabled
Elapsed Time parameter is equal to or greater than the value set in the PM

– Oper. Hours parameter

Upon a

PM – Oper. Hours warning, the following will occur:

• The TRIP/WARN LED will flash an amber 15-blink pattern
• Bit 14 in Parameter 15, Warning Status, will go to “1”
• Bit 1 in Parameter 21, Device Status, will go to “1”

Parameter 102,

PM – Oper. Hours, allows the installer to set a number of hours of

operation. It is adjustable from 0…65,565 hours.

Queue Clearing

The EC4 Current Monitoring Relay provides the capability to clear the

Trip Logs,

Warning Logs, Starts Counter, and the Elapsed Time using the Clear Queue parameter. If
using the Preventative Maintenance Flags, the user will want to reset the

Starts Count and

Elapsed Time after preventative maintenance has been performed.

Parameter 104, Clear Queue, allows the user to clear the

Trip Logs (parameters 16…20),

Warning Logs (parameters 90…94), Starts Counter (parameter 96), and the Elapsed Time
(parameter 95).
The Clear Queue parameter will clear/reset all of these parameters at the
same time.