Protective Trip and Warning Functions

Introduction

The purpose of this chapter is to provide detailed information regarding the
protective trip and warning functions of the EC4 Current Monitoring Relay. In
this chapter, you will find considerable mention given to programming
parameters as they relate to these functions. For complete descriptions of the
programming parameters, refer to Chapter 5 — Programmable Parameters.

Trip Enable

Parameter 24,

Trip Enable, allows the installer to enable or disable the desired

protective functions separately. The overcurrent, undercurrent, and
communication fault trip functions are enabled from the factory.

Warning Enable

Parameter 25,

Warning Enable, allows the installer to enable or disable the desired

warning functions separately. All warning functions are disabled from the factory.

Overcurrent Protection

The EC4 Current Monitoring Relay provides UC/OC protection through true
RMS current measurement of the individual phase currents of the connected
loads. For

Undercurrent & Overcurrent Trip and Warning Level parameters, a

warning or trip will occur when the programmed conditions are satisfied.

IMPORTANT

The EC4 Current Monitoring Relay requires undercurrent
(UC)/overcurrent (OC) to be enabled at all times. The EC4 Current
Monitoring Relay requires either UC/OC to be enabled at all times.

ATTENTION: The Trip Enable settings should not be altered during
machine operation, as unexpected behavior of the outputs could
occur. This may result in an unintended actuation of controlled
industrial equipment, with the potential for machine damage or
serious injury to personnel.