35
Installation and Wiring Chapter 2
External/Remote Reset (FRN 3.001 and later)
To reset a trip from an external/remote location, configure one of the EC4
Current Monitoring Relay’s inputs for trip reset operation using one of
parameters 83…86. Wire the input as shown in Figure 23 .
Figure 23 - External/Remote Reset Wiring
IMPORTANT
Reset operation is edge sensitive and trip free; that is, holding the
push button down (maintaining the reset contact in a closed position)
will not prevent the EC4 Current Monitoring Relay from tripping.
Reset
1-
5