External/remote reset (frn 3.001 and later) – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 34

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

35

Installation and Wiring Chapter 2

External/Remote Reset (FRN 3.001 and later)

To reset a trip from an external/remote location, configure one of the EC4
Current Monitoring Relay’s inputs for trip reset operation using one of
parameters 83…86. Wire the input as shown in Figure 23 .

Figure 23 - External/Remote Reset Wiring

IMPORTANT

Reset operation is edge sensitive and trip free; that is, holding the
push button down (maintaining the reset contact in a closed position)
will not prevent the EC4 Current Monitoring Relay from tripping.

Reset

1-

5

Advertising