Environmental specifications – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 119

Advertising
background image

120

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Appendix A Specifications

Environmental
Specifications

➊ Current ratings must be derated at altitudes greater than 2000 m

Off-State Current

0.5 mA

Transition Voltage

5...15V DC

Transition Current

0.5...2.0 mA

Table 5 - Thermistor/PTC Input Ratings

Terminals

1T1, 1T2

Type of Control Unit

Mark A

Maximum Number of Sensors

6

Maximum Cold Resistance of PTC Sensor Chain

1500

Ω

Trip Resistance

3400

Ω ± 150 Ω

Reset Resistance

1600

Ω ± 100 Ω

Short-circuit Trip Resistance

25

Ω ± 10 Ω

Maximum Voltage @ PTC Terminals (R

PTC

= 4

k

Ω)

7.5V DC

Maximum Voltage @ PTC Terminals (R

PTC

=open)

30V DC

Response Time

800 ms

Table 4 - Input Ratings

Table 6 - Environmental Specifications

Ambient Temperature

Storage
Operating
(Open)
(Enclosed)

–40

°…+85°C (–40…+185°F)

–20

°…+55°C (–4°…+131°F)

–20

°…+40°C (–4°…+104°F)

Humidity

Operating
Damp Heat – Steady State (per IEC 68-2-3)
Damp Heat – Cyclic (per IEC 68-2-30)

5…95% Non-condensing
92% r.h., 40

°C (104°F), 56 days

93% r.h., 25

°C/40°C (77°F/104°F), 21 Cycles

Cooling Method

Natural Convection

Vibration (per IEC 68-2-6)

3 G

Shock (per IEC 68-2-27)

30 G

Maximum Altitude

2000 m ➊

Pollution Environment

Pollution Degree 3

Terminal Marking

EN 50012

Degree of Protection

193-ECxxx
592-ECxxx

IP20