DeviceLogix Group

COMM OVERRIDE

This parameter is used to enable DeviceLogix
programs to override normal output behavior
in the event of a communication status
change. These events include all states
where the E3 Plus is without an I/O
connection (I/O Connection does not exist,
has timed out, has been deleted, or is
currently idle)

Parameter Number

79

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x1E-1-105

Group

DeviceLogix

Units

Minimum Value

0 = Disabled

Maximum Value

1 = Enabled

Default Value

0

NETWORK OVERRIDE

This parameter is used to enable DeviceLogix
programs to override normal output behavior
in the event of a network fault. Network
faults include duplicate MAC ID failures and
bus off conditions.

Parameter Number

80

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x1E-1-104

Group

DeviceLogix

Units

Minimum Value

0 = Disabled

Maximum Value

1 = Enabled

Default Value

0

NET OUTPUTS

This parameter monitors network outputs
controlled through DeviceLogix programs.

Parameter Number

81

Access Rule

Get/Set

Data Type

WORD

Object Mapping

0x04-1-3

Group

DeviceLogix

Units

Minimum Value

Maximum Value

Default Value

Bits

Function:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

X

Net Output 0

X

Net Output 1

X

Net Output 2

X

Net Output 3

X

Net Output 4

X

Net Output 5

X

Net Output 6

X

Net Output 7

X

Net Output 8

X

Net Output 9

X

Net Output 10

X

Net Output 11

X

Net Output 12

X

Net Output 13

X

Net Output 14

X

Advertising