Message router – class code 0x02, Devicenet object – class code 0x03 – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 124

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

125

DeviceNet Information Appendix B

The following common services are implemented for the Identity Object:

Message Router – Class
Code 0x02

No class or instance attributes are supported. The message router object exists
only to route explicit messages to other objects.

DeviceNet Object – Class
Code 0x03

The following class attributes are supported for the DeviceNet Object:

A single instance (instance 1) of the DeviceNet Object is supported. The
following instance attributes are supported:

4

Get

Revision

Major
Minor

Structure of:

USINT
USINT

4
1

5

Get

Status

WORD

Bit 0 — 0 = Not owned, 1 = Owned by
master
Bit 2 — 0 = Factory Defaulted, 1 =
Configured
Bit 8 — Minor recoverable fault
Bit 9 — Minor unrecoverable fault
Bit 10 — Major recoverable fault
Bit 11 — Major unrecoverable fault

6

Get

Serial Number

UDINT

Unique number for each device

7

Get

Product Name

String Length
ASCII String

Structure of:

USINT
STRING

Product Code-specific

8

Get

State

USINT

Returns the value “3 = Operational”

9

Get

Configuration
Consistency
Value

UINT

Unique value depending upon output of
the parameter checksum algorithm

10

Get/Set

Heartbeat
Interval

USINT

In seconds. Default = 0

Table 15 - Identity Object Common Services

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x05

No

Yes

Reset (DeviceNet only)

Table 14 - Identity Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data Type

Value

Table 16 - DeviceNet Object Class Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

2

Advertising