Ground fault current reporting, Monitor group, Current range – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 83: Frequency range

Advertising
background image

84

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 6 Current Monitoring Parameters

Ground Fault Current
Reporting

Current Range

The following chart illustrates the minimum and maximum reporting ground
fault current values for a given ground fault current range.

➊ The EC4 Current Monitoring Relay will report 0 A if the ground fault current is below 50% of the minimum

ground fault current setting for a given range.

➋ The EC4 Current Monitoring Relay is capable of reporting values greater than the maximum values shown, but

the accuracy of the value is compromised.

➌ The accuracy specified is only applicable to non-distorted sinusoidal currents.

➍ 20…100 mA for resistive loads only. For motor loads consult your local Allen-Bradley distributor

.

Frequency Range

The EC4 Current Monitoring Relay is capable of sensing variable frequency
ground fault currents ranging from 20…250 Hz.

Exception:

Any EC4 Current Monitoring Relay using an external ground fault

sensor is limited to 50/60 Hz detection.

Monitor Group

Table 22 - Ground Fault Current Reporting Summary

Ground Fault
Current Range

Minimum
Reporting
Current
➊➌

Maximum
Reporting
Current
➋➌

E3 Plus Cat. No. /Series

20…100 mA➍

10 mA

180 mA

193/592-EC3 — Series C and later

100…500 mA

50 mA

900 mA

193/592-EC3 — Series C and later

200 mA…1.0 A

100 mA

1.80 A

193/592-EC3 — Series C and later

1.0…5.0 A

500 mA

9.00 A

193/592-EC2 — Series A and later

L1 CURRENT

This parameter provides the L1 phase current
measurement in amperes.

Parameter Number

1

Access Rule

Get

Data Type

INT

Object Mapping

2C

hex

-1-231

2C

hex

-1-8

2C

hex

-1-227

Group

Monitor

Units

Amps

Minimum Value

See Table 20 -

Maximum Value

See Table 20 -

Default Value

None