Chapter 5 Programmable Parameters

OUTA DN FLTSTATE

This parameter, in conjunction with
Parameter 68, defines how Output A will
respond when a DeviceNet network fault
occurs. When set to “1”, Output A will hold
the state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by the setting of Parameter 68.

Output A can be configured to go to a desired
state in the event of a DeviceNet network
fault independent from enabling CommFault
in Parameter 24, Trip Enable.

Parameter Number

67

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-1-5

Group

DeviceNet I/O

Units

Minimum Value

0 = Go to FltValue (#68)

Maximum Value

1 = Hold Last State

Default Value

0

OUTA DN FLTVALUE

This parameter determines the state that
Output A assumes when a DeviceNet
network fault occurs and Parameter 67 is set
to “0”.

Parameter Number

68

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-1-6

Group

DeviceNet I/O

Units

Minimum Value

0 = Open

Maximum Value

1 = Closed

Default Value

0

OUTA DN IDLSTATE

This parameter, in conjunction with
Parameter 70, defines how Output A will
respond when the DeviceNet network is idle.
When set to “1”, Output A will hold the state
prior to trip occurrence. When set to “0”,
Output A will open or close as determined by
the setting in Parameter 70.

The Dn Flt parameters supersede the Dn Idl
parameters.

Parameter Number

69

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-1-7

Group

DeviceNet I/O

Units

Minimum Value

0 = Go to IdlValue (#70)

Maximum Value

1 = Hold Last State

Default Value

0

OUTA DN IDLVALUE

This parameter determines the state that
Output A assumes when the network is idle
and Parameter 69 is set to “0”.

Parameter Number

70

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-1-8

Group

Advanced Setup

Units

Minimum Value

0 = Open

Maximum Value

1 = Closed

Default Value

0

OUTB PR FLTSTATE

This parameter, in conjunction with
Parameter 72, defines how Output B will
respond when a trip occurs. When set to “1”,
Output B will continue to operate as
commanded via the network. When set to
“0”, Output B will open or close as
determined by the setting in Parameter 72.

Parameter Number

71

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x09-2-113

Group

DeviceNet I/O

Units

Minimum Value

0 = Go to FltValue (#72)

Maximum Value

1 = Ignore Fault

Default Value

0