Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 127

Advertising
background image

128

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Appendix B DeviceNet Information

The following tables indicate the I/O Assembly Data Attribute mapping for
Parameter Link-Based Assemblies:

Table 28 - Assembly Object Instance 107 Data Format (“STATUS”)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit3

Bit 2

Bit 1

Bit 0

0

Input4

Input3

Input2

Input1

OutB_Stat

OutA_Stat

Warning Faulted

Table 29 - Assembly Object Instance 141 Data Format (“DEVICELOGIX STAT”)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit3

Bit 2

Bit 1

Bit 0

0

Input4

Input3

Input2

Input1

OutB_Stat

OutA_Stat

Warning Faulted

1

Network
Output 7

Network
Output 6

Network
Output 5

Network
Output 4

Network
Output 3

Network
Output 2

Network
Output 1

Network
Output 0

2

DeviceLog
ix Enabled

Network
Output
14

Network
Output 13

Network
Output 12

Network
Output 11

Network
Output 10

Network
Output 9

Network
Output 8

Table 30 - Assembly Object Instance 184 Data Format (“PNB STATUS”)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit3

Bit 2

Bit 1

Bit 0

0

Network
Output 7

Network
Output 6

Network
Output 5

Network
Output 4

Network
Output 3

Network
Output 2

Network
Output 1

Network
Output 0

1

DeviceLogi
x Enabled

Network
Output
14

Network
Output 13

Network
Output 12

Network
Output 11

Network
Output 10

Network
Output 9

Network
Output 8

Table 31 - Assembly Object Instance 100 Attributes (“PARAMETER BASED”)

Byte

Word

Value

0

0

Value of parameter pointed to by param #61 (Low Byte)

1

Value of parameter pointed to by param #61 (High Byte)

2

1

Value of parameter pointed to by param #62 (Low Byte)

3

Value of parameter pointed to by param #62 (High Byte)

4

2

Value of parameter pointed to by param #63 (Low Byte)

5

Value of parameter pointed to by param #63 (High Byte)

6

3

Value of parameter pointed to by param #64 (Low Byte)

7

Value of parameter pointed to by param #64 (High Byte)

Table 32 - Instance 110 Data Link Output Assembly Attributes
(“PARAM LINK CMD”)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit3

Bit 2

Bit 1

Bit 0

0

Remote
Trip

Fault
Reset

Output B Output A

1

Reserved

Advertising