Programmable Parameters Chapter 5

INPUT ASSEMBLY

This parameter is used to select the desired
input assembly. See Appendix B for a listing
of available assemblies

Parameter Number

60

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-17

Group

DeviceNet Setup

Units

Minimum Value

0

Maximum Value

107

Default Value

100

ASSY WORD0 PARAM

This parameter assigns the parameter value
to be placed in Word 0 of Input Assembly
100.

Parameter Number

61

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-7

Group

DeviceNet Setup

Units

Minimum Value

0

Maximum Value

89

Default Value

21

ASSY WORD1 PARAM

This parameter assigns the parameter value
to be placed in Word 1 of Input Assembly
100.

Parameter Number

62

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-8

Group

DeviceNet Setup

Units

Minimum Value

0

Maximum Value

89

Default Value

1

ASSY WORD2 PARAM

This parameter assigns the parameter value
to be placed in Word 2 of Input Assembly
100.

Parameter Number

63

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-9

Group

DeviceNet Setup

Units

Minimum Value

0

Maximum Value

89

Default Value

2

ASSY WORD3 PARAM

This parameter assigns the parameter value
to be placed in Word 3 of Input Assembly
100.

Parameter Number

64

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-10

Group

DeviceNet Setup

Units

Minimum Value

0

Maximum Value

89

Default Value

3