Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 5 Programmable Parameters

Reset/Lock Group

L1 Loss Trip Delay

This parameter allows the installer to
program a time duration for which a loss on
line 1 must exist prior to the device tripping.

Parameter Number

128

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-115

Group

Advanced Setup

Units

0.1 Seconds

Minimum Value

0.5

Maximum Value

25.0

Default Value

0.5

L2 Loss Trip Delay

This parameter allows the installer to
program a time duration for which a loss on
line 2 must exist prior to the device tripping.

Parameter Number

129

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-116

Group

Advanced Setup

Units

0.1 Seconds

Minimum Value

0.5

Maximum Value

25.0

Default Value

0.5

L3 Loss Trip Delay

This parameter allows the installer to
program a time duration for which a loss on
line 3 must exist prior to the device tripping.

Parameter Number

130

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-117

Group

Advanced Setup

Units

0.1 Seconds

Minimum Value

0.5

Maximum Value

25.0

Default Value

0.5

TRIP RESET

This parameter provides the user with the
capability of resetting a trip over the
DeviceNet network. After a trip is reset, the
parameter automatically returns to a
“Ready” state.

Parameter Number

26

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0x29-1-126

Group

Reset/Lock

Units

Minimum Value

0 = Ready

Maximum Value

1 = Reset

Default Value

0