Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 62
Rockwell Automation Publication 193-UM011A-EN-P - September 2010
63
Programmable Parameters Chapter 5
GF TRIP LEVEL
This parameter sets the ground fault trip
level.
Parameter Number
37
Access Rule
Get/Set
Data Type
USINT
Object Mapping
2C
hex
-1-137
Group
Advanced Setup
Units
Amps
Minimum Value
0.02
Maximum Value
5.0
Default Value
2.5
GF WARN LEVEL
This parameter sets the ground fault warning
level.
Parameter Number
38
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0xB4-1-1 (E3)
2C
hex
-1-138 (E3 Plus)
Group
Advanced Setup
Units
Amps
Minimum Value
0.02
Maximum Value
5.0
Default Value
2.0
CT RATIO ➊
This parameter defines the turns ratio of the
primary current transformers (when used).
See Table 20 - on page 83 for the
corresponding FLA setting ranges.
➊ FRN 2.000 and later.
Parameter Number
78
Access Rule
Get/Set
Data Type
USINT
Object Mapping
0x2-1-178
Group
Overload Setup
Units
—
Minimum Value
0 = 50:5
1 = 100:5
2 = 150:5
3 = 200:5
4 = 300:5
5 = 500:5
6 = 600:5
7 = 800:5
8 = 1200:5
9 = 2500:5
Maximum Value
10 = 5000:5
Default Value
0 = 50:5