GF TRIP LEVEL

This parameter sets the ground fault trip
level.

Parameter Number

37

Access Rule

Get/Set

Data Type

USINT

Object Mapping

2C

hex

-1-137

Group

Advanced Setup

Units

Amps

Minimum Value

0.02

Maximum Value

5.0

Default Value

2.5

GF WARN LEVEL

This parameter sets the ground fault warning
level.

Parameter Number

38

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0xB4-1-1 (E3)
2C

hex

-1-138 (E3 Plus)

Group

Advanced Setup

Units

Amps

Minimum Value

0.02

Maximum Value

5.0

Default Value

2.0

CT RATIO ➊

This parameter defines the turns ratio of the
primary current transformers (when used).
See Table 20 - on page 83 for the
corresponding FLA setting ranges.

➊ FRN 2.000 and later.

Parameter Number

78

Access Rule

Get/Set

Data Type

USINT

Object Mapping

0x2-1-178

Group

Overload Setup

Units

Minimum Value

0 = 50:5

1 = 100:5

2 = 150:5

3 = 200:5

4 = 300:5

5 = 500:5

6 = 600:5

7 = 800:5

8 = 1200:5

9 = 2500:5

Maximum Value

10 = 5000:5

Default Value

0 = 50:5