DeviceNet Information Appendix B

ODVA Fault Codes

The following ODVA fault codes are returned by the Control Supervisor Object
instance attribute 13 “TripCode:”

13

Get/Set

COS Mask

WOR
D

0

Change of state mask for
DeviceNet

15

Get/Set

AutoBaudEnabl
e

BOOL

0…1

1

1 = Enabled

16

Get/Set

Output
Assembly

USINT

2, 101, 103,
104, 105,
140

103

Output Assembly
instance that is active

17

Get/Set

Input Assembly

USINT

50, 51, 100,
106, 107,
141, 184

100

Input Assembly instance
that is active

18

Get/Set

Program Lock

BOOL

0…1

0

0 = Unlocked
1 = Locked

19

Get/Set

Set To Defaults

BOOL

0…1

0

0 = No action
1 = Reset

20

Get

Device
Configuration

WOR
D

0…7

Bit 0 set = 4 in/2 out

hardware present

Bit 1 set = PTC hardware

present

Bit 2 set = Ground Fault

hardware present

50

Get/Set

PNB COS Mask

WOR
D

0…0xFF

0

Change of State mask
for PNB

Table 64 - DeviceNet Interface Object Common Services

Service
Code

Implemented for:

Service
Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Table 63 - DeviceNet Interface Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Min/Max

Defau
lt

Desc.

Table 65 - ODVA Fault Codes

Trip Code

Description

Trip Code

Description

62

Memory Fault

73

Starts/Hour Exceeded

10

Test Trip

102

Comm Fault

11

Remote Trip

103

Comm Idle Fault

23

L1 Loss

108

L2 Undercurrent

24

L2 Loss

109

L3 Undercurrent

25

L3 Loss

110

L1Overcurrent

27

Ground Fault

111

L2Overcurrent