141

DeviceNet Information Appendix B

Table 58 - Control Supervisor Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Value

10

Get

Tripped

BOOL

0 = No Fault present
1 = Fault Latched

11

Get

Warning

BOOL

0 = No Warning present
1 = Warning present (not latched)

12

Get/Set

Fault Reset

BOOL

0->1 = Trip Reset
otherwise no action

13

Get

Trip Code

UINT

ODVA Trip Code – In trip state indicates
cause of trip; If not tripped, indicates cause
of last trip.

14

Get

Warning Code

UINT

ODVA Warning Code - In warning state
indicates cause of warning; If no warning,
indicates cause of last warning.

17

Get/Set

Force Trip

BOOL

0->1 = Trip. Test trip generated. This
attribute returns object state conflict when
“Test Enable” bitr is set in Trip Enable.

100

Get

Elapsed Time

UINT

Logs motor-on (Current Present) hours.

101

Get

Starts Counter

UINT

Logs the number of motor starts.

106

Get/Set

PM – Start Count

UINT

The Preventative Maintenance Start Count
flag is set after this number of starts

107

Get/Set

PM – Oper Hours

UINT

The Preventative Maintenance Operating
Hours flag is set after this number of hours

108

Get/Set

Test Enable

BOOL

Enables/Disables the Test Button.

109

Get

Warning Log 0

WORD

Enumerated same as attribute 115

110

Get

Warning Log 1

WORD

Enumerated same as attribute 115

111

Get

Warning Log 2

WORD

Enumerated same as attribute 115

112

Get

Warning Log 3

WORD

Enumerated same as attribute 115

113

Get

Warning Log 4

WORD

Enumerated same as attribute 115

114

Get

Trip Status

WORD

Bit 0 = Test Trip
Bit 1 = Overload
Bit 2 = Phase Loss
Bit 3 = Ground Fault **
Bit 4 = Stall
Bit 5 = Jam
Bit 6 = Underload
Bit 7 = PTC **
Bit 8 = Current Imbal
Bit 9 = Comm Fault
Bit 10 = Comm Idle
Bit 11 = NonVol Mem
Bit 12 = Hardware Fault
Bit 13 = Reserved
Bit 14 = Remote Trip
Bit 15 = Blocked Start

Advertising