Acknowledge handler object – 0x2b – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 142

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

143

DeviceNet Information Appendix B

The following common services are implemented for the Control Supervisor
Object:

Acknowledge Handler
Object – 0x2B

The following class attributes are supported for the Acknowledge Handler
Object:

A single instance (instance 1) of the Acknowledge Handler Object is supported.
The following instance attributes are supported:

126

Get/Set

Trip Reset

BOOL

0->1 = Trip Reset
otherwise no action

130

Get/Set

Reset Mode

BOOL

0 = Manual
1 = Automatic

131

Get/Set

OL Reset Level

USINT

%FLA

132

Get/Set

Clear Queues

BOOL

0->1 = Clear fault and warning queues, start
counters and operating hour accumulators
otherwise no action

177

Get/Set

IN1 Assignment

USINT

0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed

178

Get/Set

IN2 Assignment

USINT

0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed

179

Get/Set

IN3 Assignment

USINT

0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed

180

Get/Set

IN4 Assignment

USINT

0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = 2 Speed

Table 59 - Control Supervisor Object Common Services

Service
Code

Implemented for:

Service
Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x05

No

Yes

Reset

Table 58 - Control Supervisor Object Instance Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Value

Table 60 - Acknowledge Handler Object Class Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

1