Current Monitoring Parameters Chapter 6

➊ 0 A is reported when the actual current is below the indicated minimum reporting current.

➋ The E3 is capable of reporting higher currents, but reporting accuracy is compromised.

Reporting Accuracy

Table 20 - Current Reporting Summary (with indicated precision)

FLA Setting Range
[A]

CT Ratio

Min. Reporting
Current [A]

Max Reporting
Current [A]

0.4…2.0

0.15

14.40

1…5

0.30

36.00

3…15

0.90

108.00

5…25

1.50

180.00

9…45

3.0

360.0

18…90

6.0

720.0

9…45

50:5

3

360

18…90

100:5

6

720

28…140

150:5

9

1080

42…210

200:5

12

1440

60…302

300:5

18

2160

84…420

500:5

30

3600

125…630

600:5

36

4320

172…860

800:5

48

5760

240…1215

1200:5

72

8640

450…2250

2500:5

150

18000

1000…5000

5000:5

300

32767

Table 21 - Current Reporting Accuracy

FLA Setting Range

Operating Range

100% Min. current rating…
720% Max. current rating

50% Min. current rating…
100% Min. current rating

0.4…2.0 A

±10%

All others

±6%

±10%

IMPORTANT

The accuracy specified above is only applicable to non-distorted
sinusoidal currents.