Warning history codes – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 93

Advertising
background image

94

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 8 Trip History and Snapshot

Warning History Codes

Code Type

Description

0

No Fault

No Fault Conditions Detected

1

Ground Fault

Power conductor or motor winding is shorting to ground

2

L1 Undercurrent

Line 1 current is lower than the programmed level

3

L2 Undercurrent

Line 2 current is lower than the programmed level

4

L3 Undercurrent

Line 3 current is lower than the programmed level

5

L1 Overcurrent

Line 1 current exceeds the programmed level

6

L2 Overcurrent

Line 2 current exceeds the programmed level

7

L3 Overcurrent

Line 3 current exceeds the programmed level

8

L1 Loss

Current in line 1 is not present

9

L2 Loss

Current in line 2 is not present

10

L3 Loss

Current in line 3 is not present

11

Comm Fault

DeviceNet communications fault detected

12

Comm Idle

DeviceNet idle condition detected

13

Config Fault

Parameter configuration fault. Check configuration parameters for the
proper values.

14

PM - # Starts

Number of starts has exceeded the programmed level

15

PM- Oper. Hours

Number of operating hours has exceeded the programmed level

TripHistory Mask

This parameter allows the user to configure
which current based protection features are
written to the five record Trip History as
outlined in the table below:

1 = Recorded
0 = Not Recorded

Parameter Number

142

Access Rule

Get/Set

Data Type

UINT

Object Mapping

0Fhex-8E-01

Group

TripWarn History

Units

Minimum Value

0000000000000000

Maximum Value

1111111111111111

Default Value

1101111101111111

Bit

Function:

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

X

Ground Fault

X

L1 Undercurrent

X

L2 Undercurrent

X

L3 Undercurrent

X

L1 Overcurrent

X

L2 Overcurrent

X

L3 Overcurrent

X

L1 Loss

X

L2 Loss

X

L3 Loss

X

Comm Fault

X

Comm Idle

X

Hardware Fault

X

Test Trip

X

Remote Trip

X

NonVol Mem Fault

Advertising