Rockwell Automation Publication 193-UM011A-EN-P - September 2010

73

Programmable Parameters Chapter 5

DeviceNet Setup Group

PROGRAM LOCK

This parameter prohibits the device
parameters from being altered when set to
“Locked”.

This parameter must be set to “Unlocked” to
allow parameter modification.

Parameter Number

53

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0xB4-1-18

Group

Reset/Lock

Units

Minimum Value

0 = Unlocked

Maximum Value

1 = Locked

Default Value

0

SET TO DEFAULTS

This parameter allows the user to reset the
parameter settings to the factory default
values. After parameter values have been
reset to the factory default settings, the
parameter automatically returns to a
“Ready” state.

Parameter Number

54

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0xB4-1-19

Group

Reset/Lock

Units

Minimum Value

0 = Ready

Maximum Value

1 = Set

Default Value

0

Test Enable

This parameter allows the installer to enable
or disable the test function of the Test/Reset
button.

Parameter Number

103

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

29hex-1-108

Group

Reset/Lock

Units

Minimum Value

0 = Disable

Maximum Value

1 = Enable

Default Value

1

Clear Queue

This parameter allows the user to clear the
Trip Logs, Warning Logs, Starts Counter, and
the Elapsed Time. Setting the Clear Queue
parameter to "1" will clear/reset the Trip
Logs, Warning Logs, Starts Counter, and the
Elapsed Time parameters at the same time.

Parameter Number

104

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

29hex-1-132

Group

Reset/Lock

Units

Minimum Value

0 = Ready

Maximum Value

1 = Clear

Default Value

0

AUTO BAUD ENABLE

When this parameter is enabled, the device
will attempt to determine the network baud
rate and set its baud rate to the same,
provided network traffic exists.

At least one node with an established baud
rate must exist on the network for autobaud
to occur.

Parameter Number

55

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

0xB4-1-15

Group

DeviceNet Setup

Units

Minimum Value

0 = Disabled

Maximum Value

1 = Enabled

Default Value

1