Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Appendix B DeviceNet Information

The following instances 5…7 (Group 3 Explicit Message Connections Allocated
through UCMM) are supported:

The following common services are implemented for the Connection Object:

12

Get/Set

Watchdog Action

USINT

0 = Transition to timed out
1 = Auto delete
2 = Auto reset

13

Get

Produced Connection
Path Length

UINT

8

14

Get/Set

Produced Connection
Path

EPATH

21 04 00 25 (assy. inst.) 00 30 03

15

Get

Consumed Connection
Path Length

UINT

8

16

Get/Set

Consumed Connection
Path

EPATH

21 04 00 25 (assy. inst.) 00 30 03

Table 38 - Connection Object Instances 5…7 Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Value

1

Get

State

USINT

0 = Nonexistent
1 = Configuring
3 = Established
4 = Timed out

2

Get

Instance Type

USINT

0 = Explicit Message

3

Get

Transport Class Trigger

BYTE

0x83 — Server, Transport Class 3

4

Get

Produced Connection ID

UINT

Depends on message group
and message ID

5

Get

Consumed Connection ID

UINT

Depends on message group
and message ID

6

Get

Initial Comm
Characteristics

BYTE

0x33 (Group 3)

7

Get

Produced Connection Size UINT

0

8

Get

Consumed Connection
Size

UINT

9

Get/Set

Expected Packet Rate

UINT

in ms

12

Get

Watchdog Action

USINT

01 = Auto delete
03 = Deferred delete

13

Get

Produced Connection
Path Length

UINT

0

14

Get

Produced Connection
Path

Empty

15

Get

Consumed Connection
Path Length

UINT

0

16

Get

Consumed Connection
Path

Empty

Table 37 - Connection Object Instance 4 Attributes

Attribute
ID

Access
Rule

Name

Data
Type

Value