Devicenet troubleshooting procedures, Input and output troubleshooting procedures, Loss of node address – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 115

Advertising
background image

116

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

Chapter 11 Troubleshooting

DeviceNet Troubleshooting
Procedures

The following table identifies possible causes and corrective actions when
troubleshooting DeviceNet related failures using the

NETWORK STATUS

LED.

Loss of Node Address

Please refer to DeviceNet Node Commissioning on page 4-48 for further
information regarding node commissioning.

Input and Output
Troubleshooting
Procedures

Configuration
Fault
(warning)

1. Parameter 27, Single/Three Ph, is set to single phase and

current is being sensed in phase L3 during motor operation.

2. FLA setting is outside the “legal” range, as determined by the

corresponding CT Ratio setting.

1. For three-phase applications, Parameter 27, Single/Three Ph, should

be set to “three-phase”.

2. See Table 20 - and program the FLA setting within the range

specified.

Remote Trip

1. Contact closure of remote sensor (e.g., vibration switch).

1. Take corrective action to address the issue that caused the sensor to

actuate.

2. Check sensor for proper operation.
3. Check wiring.

PM - # Starts

(warning)

1. Parameter 96, Starts Counter, is equal to or greater than the

value set in parameter 101, PM - # Starts.

1. Set parameter 104, Clear Queue, to reset parameter 96, Starts

Counter.

PM – Oper.
Hours
(warning)

1. Parameter 95, Elapsed Time, is equal to or greater than the

value set in parameter 102, PM – Oper. Hours.

1. Set parameter 104, Clear Queue, to reset parameter 95, Elapsed

Time.

Table 24 - Trip/Warn LED Troubleshooting Procedures

Table 25 - DeviceNet Troubleshooting Procedures

Color

State

Possible Cause

Corrective Action

None

1. The EC4 Current Monitoring Relay is not receiving power

at the DeviceNet connector.

1. Check DeviceNet power and cable connections and the power

connection on the DeviceNet connector.

Green
Red
Off

Flashing 1. The E3 or EC4 Current Monitoring Relay is trying to

determine the network baud rate

1. The current monitoring relay can not determine the network baud rate

if no network traffic exists. Network traffic can be induced by
invoking a Network Who using DeviceNet Manager.

Green

Flashing 1. Current Monitoring Relay is on-line but not allocated to a

master.

1. Check DeviceNet master and its scan list for correct scanner

configuration.

Green

Solid

1. Normal operating state, and the EC4 Current Monitoring

Relay is allocated to a master.

1. No action required.

Red

Flashing 1. I/O connection timed-out

1. Reset DeviceNet master device.

Red

Solid

1. Diagnostics test failed on power-up/reset. Internal fault

exists.

2. Duplicate DeviceNet node address exists (two DeviceNet

nodes cannot have the same address).

3. Invalid baud rate (if autobaud is disabled).

1. Cycle power to the unit and network. If the fault still exists, replace

unit.

2. Change the value of Parameter 57, NonVol MAC ID, to a valid address

and reset the device.

3. This will only occur if Parameter 55, AutoBaudEnable, is set to

“disabled”. Set Parameter 55 to “enabled” and reset the EC4 Current
Monitoring Relay (or) set Parameter 56, NonVol Baud Rate, to the
correct setting and reset the EC4 Current Monitoring Relay.

ATTENTION: If the outputs are to be commanded via an explicit
message, ensure that there can never be an established I/O
connection that can actively control them, and that the explicit
message connection has a non-zero expected packet rate (EPR)
setting.